Supply
In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. The body of the electrical device is connected with earth via this earth connection at the transformer. This arrangement is a current standard for residential and industrial electric systems particularly in Europe.
The conductor that connects the exposed metallic parts of the consumer's electrical installation is called protective earth (PE). The conductor that connects to the star point in a three-phase system, or that carries the return current in a single-phase system, is called neutral (N). Three variants of TN systems are distinguished.
TN−S: PE and N are separate conductors that are connected together only near the power source.
TN−C: a combined PEN conductor fulfils the functions of both a PE and an N conductor (on 230/400 V systems normally only used for distribution networks).
TN−C−S: part of the system uses a combined PEN conductor, which is at some point split up into separate PE and N lines. The combined PEN conductor typically occurs between the substation and the entry point into the building, and earth and neutral are separated in the service head. In the UK this system is also known as protective multiple earthing (PME); similar systems are designated MEN in Australia and New Zealand and MGN in North America.
It is possible to have both TN-S and TN-C-S supplies taken from the same transformer. The PEN must be suitably reinforced against failure, as an open-circuit PEN can impress full phase voltage on any exposed metal connected to the system earth downstream of the break. The alternative is to provide a local earth and convert to TT. The main attraction of a TN network is that the low impedance earth path allows easy automatic disconnection of supply (ADS) in the case of a line-to-PE short circuit, and an RCD is not needed to detect earth faults.